23
Gram
Commercial
Technical information
765041466
Description :
Operation- and servicemanual
Gram Process KPS
Compiled. Latest revision. Deleted.
Date Name Date Name Rev.no Date Name
30.09.11 JP 000
Use the keys and to scroll all the controller parameters.
Press to confirm your choice.
Use the keys and to select the new value of the parameter.
Press to confirm your choice.
Press several times to exit.
Parameters.
Paramete
r
Description Default Min. Max.
Positive quick cooling
P01 Room temperature setpoint, soft
-5C -30C 30C
P02 Room temperature setpoint, hard
-25C -40C 30C
P03 Probe temperature setpoint, soft
3C -30C 30C
P04 Probe temperature setpoint, hard
20C -30C 30C
P05 Process duration 90 min 0 min 900 min
P06 Hard phase duration expressed in % relative to P05 60% 0% 100%
P07 Room temperature setpoint, storing
2C -30C 30C
Negative quick cooling
N01 Room temperature setpoint
-25C -40C 30C
N02 Probe temperature setpoint
-18C -30C 30C
N03 Process duration 240 min 0 min 900 min
N04 Room temperature setpoint, storing
-22C -40C 30C
A
larms
A01 Temperature alarm hysteresis
2C 0C 10C
A02 High temperature alarm, relative to P07
10C 0C 50C
A03 Low temperature alarm, relative to P07
-10C -50C 0C
A04 High temperature alarm, relative to N04
10C 0 50C
A05 Low temperature alarm, relative to N04
-10C -50C 0C
A06 Temperature alarm delay from storing or defrost start 60 min 0 min 30 min
A07 Temperature alarm delay 30 min 0 min 300 min
A08 Duration of the buzzer in alarm mode 1 min 0 min 240 min
MENU