24
Gram
Commercial
Technical information
765041466
Description :
Operation- and servicemanual
Gram Process KPS
Compiled. Latest revision. Deleted.
Date Name Date Name Rev.no Date Name
30.09.11 JP 000
Paramete
Description Default Min. Max.
Display
D01 Temperature unit of measurement
(0=Celsius, 1=Fahrenheit)
0 0 1
D02 Room sensor offset
0C -10C 10C
D03 Display backlight
(0 when pressing a key; 1 always on)
1 0 1
D04 Core probe offset
-7C -10C 10C
D05 Surface probe offset
-7C -10C 10C
D06 External probe offset
-7C -10C 10C
Defrost
S01 Performs defrost on quick cooling start
(0=no; 1=yes)
0 0 1
S02 End of defrost temperature
8C -10C 30C
S03 Defrost max. duration 15 min 1 min 90 min
S04 Interval between defrosts in storing (0=excluded) 0 hrs 0 hrs 18 hrs
S05 Type of defrost:
0=electrical or due to compressor stop
1=hot gas
2=air
2 0 2
S06 Dripping time 1 min 0 min 90 min
S07 Compressor activation delay with hot gas defrost 0 sec 0 sec 600 sec
S08 First defrost activation time from storing start
(0=excluded)
0 0 90 min
S09 Ignores compressor protection delays in defrost 0 0 1
S10 Defrost type started through keyboard:
0=electrical or due to compressor stop
1=hot gas
2=air
2 0 2
Configuration
C01 Door input (0=de-activated; 1=activated) 1 0 1
C02 Door open polarity 0 0 1
C03 Door open alarm delay 2 min 0 min 60 min
C04 Activates buzzer (0=de-activated; 1=activated) 1 0 1
C05 Buzzer duration at the end of process 10 sec 0 600 sec
C06 Temperature difference in the first phase of probe
insertion test (0=test excluded)
7C
0
60C
C07 Duration of the second phase of probe insertion test
(0=test excluded)
56 sec 0 600 sec
C08 Activates condenser sensor
0=no sensor
1=sensor
1 0 1
C09 Compressor stop delay due to door opening 30 sec 0 sec 60 sec
C10 Pressostat alarm detection time 5 sec 0 sec 60 sec
C11 High pressure digital input polarity 0 0 1
C12 Heaters starting setpoint
-5C -10C -20C