9 - BOILER SERVICING
Fig. 19 - 50/70, 70/90 baffles
8 Replace the front cleaning door, ensuring the seal
is in good condition and secure it in position with
the nuts and washers previously removed. Tighten
to form a seal.
9 Remove the condensate trap and check that it is not
blocked and is operating correctly, i.e. the float is
free to move. Clean the trap and float as required.
Refer to Section 5.7.
10 Check that the boiler condensate outlet is
unobstructed. Clean if necessary.
Fig. 20 - 90/120 baffles
RIGHT
BAFFLES
LEFT
BAFFLES