D Series Modular Air-cooled Scroll Chillers 
6
Fig.1-1 Schematic Diagram
2 Product Data and Operating Range 
(1) See  the  Data  Sheet  for  detailed  product  data.  Data  on  the  product  nameplate  always  takes 
precedence. If there is any special requirement, consult the local sales oce for model selection. 
(2) Maximum and minimum water operating pressures.
 
y
The maximum inlet water pressure is 1.0×10
6
  Pa.
 
y
The minimum inlet water pressure is  0.2×10
6
  Pa.
(3) Operating Range
Item
Water Side Air Side
Water Flow
 m
3
/ (h·kW)
Leaving Water 
Temperature (
℃
)
DB Temperature (
℃
)
WB Temperature
(
℃
)
Cooling
0.172
7 35 —
Heating (Heat Pump) 45 7 6
Item
Water Side Air Side
Leaving Water 
Temperature 
(
℃
)
Chilled Water 
Temperature Dierence 
(
℃
)
Ambient DB Temperature 
(
℃
)
Cooling 5
~
15 2.5
~
6
15
~
48(R22)
15
~
45(R410A)
Heating (Heat Pump) 40
~
50 2.5
~
6 -15
~
24