D Series Modular Air-cooled Scroll Chillers
32
6.3 Wiring of the Electric Control Cabinet
6.4 Filed Wiring
Safety Code
(1) All wiring shall comply with applicable codes and engineering requirements.
(2) All eld wiring shall be performed by the qualied electrician.
(3) Never perform wiring before the power supply is cut o󰀨.
(4) Any damage caused by the improper external wiring shall be at the installer’s expense.
WARNING
Only copper conductor is allowed.
The power cord is wired into the internal electric box
(1) The power cord must be routed inside the conduit.
(2) The power cord must enter the electric box through a rubber or plastic ring to avoid any damaged
caused by the sharp edge of the metal sheet.
(3) The power cord close to the electric box must be attached securely to prevent the terminal block of the
electric box a󰀨ected by the outside force.
(4) The unit shall be grounded reliably and never connect the ground wire with the gas fuel pipe, water
pipe, lightening rod or telephone line.
Control Line
(1) The eld supplied control line shall be at a minimum 1mm
2
.
(2) The electric box will send the control signal (220 AC, 5A) to control the chilled water pump and auxiliary
electric heater, however, never do not drive them directly through the control signal but through their
AC contactors.
(3) A reasonable length of the control line should be left outside the unit and the rest should be bundled
and fed into the electric box.