D Series Modular Air-cooled Scroll Chillers
14
Blind plug
NOTE
Keep the purge valve of the water system open in order to drain the evaporator and condenser
completely.
Diameters of Entering/Leaving Water Pipes
Diamter
(mm)
Cooling load
(kW)
DN15 0~3
DN20 3~7
DN25 5~13
DN32 10~25
DN40 15~38
DN50 29~75
DN65 46~126
DN80 84~230
DN100 167~461
DN125 314~586
DN150 523~1151
DN200 1068~2094