Rooftop Packaged
14
5 Electrical Installation
5.1 Electrical Date and Wire Sizing
Model Name
Power Supply
(V, Ph, Hz)
Capability
of Air
Switch(A)
Min.
Sectional
Area of
Earth
Wire(mm
2
)
Min.
Sectional
Area of
Power
Cord(mm
2
)
GK-H03NH3AS
220-240V,1Ph,
50/60Hz
25A
4.0
4.0
GK-H5.5NH3AS
220-240V,1Ph,
50/60Hz
40A
10.0
10.0
GK-H5.5NH3AF
220-240V,3Ph,
60Hz
40A
10.0
10.0
GK-H10NH3AF
220-240V,3Ph,
60Hz
50A
10.0
10.0
GK-H15NH3AF
220-240V,3Ph,
60Hz
125A
35.0
35.0
5.2 Connect Wiring to the Terminals
NOTICE
!
Please note the following items before installing the electric appliance.
①.
Check if the power supply accords with its value on the nameplate.
②.
The capacity of the power supply must be large enough.
③.
The circuit should be installed by the professional technician.
④.
In fixed circuit, there must be electricity leakage protection switch of
enough power capacity and air switch with space between its electrode
contacts
3mm.
⑤.
Single wire connection.
a) Peel off the insulation for 25mm with pliers.
b) Remove the screw from the terminal board.
c) Bend the peeled wire into circle with pliers.
d) Screw cross the circle and fix it on the terminal board.
⑥.
Strand wires connection.
a) Peel off the insulation for 10mm with pliers.
b) Remove the screw from the terminal board.
c) Clamp a round terminal of the peeled wires.

Related product manuals