GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
227
2.2.4.127 PC Compressor drive current detecting circuit error
Error display:
ODU mainboard will display
Error judgment condition and method:
Check the error code on nixie tube of ODU main control board. If PC is displayed, it indicates
compressor drive current detecting circuit error
Possible reason
Compressor drive board is abnormal
Troubleshooting:
2.2.4.128 PH Compressor drive DC bus high voltage protection
Error display:
ODU mainboard will display
Error judgment condition and method:
If the mainboard detects that input power cord voltage exceeds 460V, it will report high voltage
protection.
Possible reason
Power supply voltage is higher than 460V;
Compressor drive board is abnormal.
Troubleshooting:
2.2.4.129 PL Compressor drive DC bus low voltage protection
Error display:
ODU mainboard will display