GREE                                                                        GMV5E DC INVERTER VRF UNITS SERVICE MANUAL 
    228   
Error judgment condition and method: 
If the mainboard detects that input power cord voltage is lower than 320V, it will report low voltage 
protection. 
Possible reason: 
■Power supply voltage is lower than 320V; 
■Compressor drive board is abnormal. 
Troubleshooting: 
 
2.2.4.130 “PJ” Inverter compressor startup failure 
Error display: 
ODU mainboard will display
 
Check  the error  code on  nixie  tube of  ODU  main  control  board.  If PJ  is  displayed,  it  indicates 
inverter compressor startup failure 
■Poor contact of compressor UVW wire; 
■Compressor is broken; 
■Compressor drive board is broken;