GMV DC Inverter VRF
60
Meaning
Progress
LED1 LED2 LED3
Code
Display
Code
Display
Code
06_outdoor unit's
parts inspection
db ON 06 ON OC ON
The system detected that
there's no fault for outdoor
unit's parts. Then it will
automatically enter into
If an abnormality is detected, it will stay in the current state and manual troubleshooting is
required. The corresponding faults are as below:
Meaning
Progress
Code
Display
Code
Display
Code
Display
06_outdoor unit's
parts inspection
db ON 06 ON
Corresponding
error code
ON
The system detected that
there's fault for outdoor
Refer to the part of “Troubleshooting” for the corresponding troubleshooting method.
Step 10: The unit debugging step 07 is “indoor unit's parts inspection”.
If there is no abnormality in the detection, the display is as below, and then it automatically enters
the next step of detection.
Meaning
Progress
Code
Display
Code
Display
Code
Display
07_indoor unit's
parts inspection
db ON 07 ON OC ON
The system detected
that there's no fault for
indoor unit's parts. Then
it will automatically enter
If an abnormality is detected, it will stay in the current state and manual troubleshooting is
required. The corresponding faults are as below:
—— Debugging code Progress code Status code
Meaning
Progress
Code
Display
Code
Display
Display
07_
inspection
db ON 07 ON
XXXX/
correspodin
ON
The system detected that
there's fault for indoor
XXXX indicates the engineering no. of fault indoor unit. 3s later, the corresponding error code will
be displayed. For example, if d5 fault occurs for No.100 indoor unit, LED3 displays as below: 01 (2s
later) 00(2s later) d5, and they will display like that circularly.
Refer to the part of “Troubleshooting” for the corresponding troubleshooting method.
Step 11: The debugging step 08 is “compressor preheat confirmation”.
If the preheat time has reached for 2h, the display is as below. Then it will enter into the next step
for inspection.