2.140 "U3" Power Phase-Sequence Protection
Fault display: main board of outdoor unit, wired controller of indoor unit and receiver of indoor unit
display
Fault diagnosis:
Check the three-phase power of the unit. If the power is connected incorrectly, thereby causing phase
loss or reverse phase, the unit generates a fault.
Possible causes:
The power is connected wrongly or phase loss or reverse phase occurs
Abnormal detection circuit
Troubleshooting:
"U3" Power Pha se-
Sequence Protection
The detection circuit may
operate improperly
Yes
Whether the
three-pha se power supply is
connected prope rly?
No
Replace th e main control
board
2.141 "U4" Refrigerant Loss Protection
Fault display: main board of outdoor unit, wired controller of indoor unit and receiver of indoor unit
display
Fault diagnosis:
Check the high pressure and the low pressure of the unit by the pressure sensor. If the temperatures
corresponding to the high pressure and the low pressure of the unit are below the ambient temperature
for over 5, the unit will not start operation for safety purpose.
Possible causes:
■ Insufficient refrigerant in the unit;
The pipes leak.
Troubleshooting:

Other manuals for Gree GMV-335WM/G-X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-335WM/G-X and is the answer not in the manual?

Gree GMV-335WM/G-X Specifications

General IconGeneral
BrandGree
ModelGMV-335WM/G-X
CategoryInverter
LanguageEnglish

Related product manuals