DC Inverter Side Discharge VRF Ⅱ for North America
74
Total capacity of downstream indoor units
5.5 Dimension of Pipe between Indoor Branch and IDU
Dimension of pipe between indoor branch and IDU should be consistent with the
dimension of indoor pipe.
Fig. 9
NOTICE! If the distance between IDU and its nearest branch is over 10m(33feet),
then the liquid pipe of IDU (rated capacity ≤17000Btu/h) shall be enlarged.