3. As shown in the figure below, put the black test probe to pad P and the red test probe to pad V (YE) 
(make sure the moisture proof tape is removed). In normal cases, the multimeter should read 0.39±0.3 V. 
If it is ―0‖ or infinitely great, the IPM module is faulty. 
 
4. As shown in the figure below, put the black test probe to pad P and the red test probe to pad W (RD) 
(make sure the moisture proof tape is removed). In normal cases, the multimeter should read 0.39±0.3 V. 
If it is ―0‖ or infinitely great, the IPM module is faulty. 
 
5. As shown in the figure below, put the black test probe to pad U (BL) and the red test probe to pad NU 
(make sure the moisture proof tape is removed). In normal cases, the multimeter should read 0.39±0.3 V. 
If it is ―0‖ or infinitely great, the IPM module is faulty.