GMV5 DC INVERTER VRF UNITS SERVICE MANUAL 
183 
 
6. As shown in the figure below, put the black test probe to pad V (YE) and the red test probe to pad NV 
(make sure the moisture proof tape is removed). In normal cases, the multimeter should read 0.39±0.3 V. 
If it is ―0‖ or infinitely great, the IPM module is faulty.