Press the SW4 back button on the master module to return to the previous process or exit the function 
setting status. 
The default status is 00, that is, no silence. 
4.2.3.4 A8 After-Sales Vacuum Pumping Mode 
Introduction: 
This function is used to ensure the vacuum of the entire system during maintenance and to avoid 
dead pipeline zones. When this function is set, both the expansion valve and the solenoid valve of the 
unit will open. 
Setting steps: 
Step 1: 
Enter A8 after-sales vacuum pumping mode, and ensure that the master module displays 
as follows: 
LED1  LED2  LED3 
A8  On  00  Blinks  OC  Blinks 
The system enters the to-be-confirmed status of vacuum pumping mode. 
Step 2: 
Press the SW3 button. The system enters the confirmed status of vacuum pumping mode 
and all modules display as follows: 
LED1  LED2  LED3 
Function code  Display status  Current process  Display status  Current status  Display status 
A8  On  00  On  OC  On 
At this time, the expansion valves of all indoor and outdoor units are open, and the entire system 
cannot be started. 
When you press the SW4 back button on the master unit for over 5 seconds or the vacuum pumping 
status remains for 24 hours, the entire system exits the status. 
4.2.3.5 n0 Auto Energy Saving 
Introduction: 
This function sets the user-required energy saving mode. The default mode is capability priority 
control. 
After energy saving mode is set, the system capability will deteriorate. 
Code  Function Name 
01  Capability priority control (default setting) 
02  Energy saving priority control 
Setting steps: 
Step 1:
 Enter n0 system energy saving operation, and ensure that the master unit displays as follows: 
LED1  LED2  LED3 
Function code  Display status 
Display status  Current status  Display status 
n0  On  01  Blinks  OC  Blinks 
Step 2:
 Press the SW1 up button and the SW2 down button to select the corresponding mode.