GMV DC Inverter VRF 
62 
If the unit has detected the abnormal status, the display is as below:   
Meaning 
Progress 
Code 
Display 
Code 
Display 
Code
Display 
main pipeline before 
db  ON  10  ON  U6  ON  Main pipeline is abnormal   
At this time, it is necessary to check whether the gas valve and the liquid valve are completely 
open or whether the main pipeline is blocked. Once inspection is completed, you can return to the 
previous step by pressing SW4 button to re-enter the judgment. 
If inspection valve of the unit is normal, the display is as below. The unit will automatically enter 
into the next step.   
——  Debugging code  Progress code  Status code   
Meaning 
Progress 
Code 
Display 
Display 
Code
Display 
main pipeline before 
db  ON  10  ON  OC  ON 
The main pipeline is turned on 
normally   
Step 14: Unit debugging step 11 is “reserved function”. 
The main module display is as below. The unit automatically enters into the next step.   
Meaning 
Progress 
Code 
Display 
Display 
Code
Display 
11_ reserved function  db  ON  11  ON  AE  ON 
——
 
Step 15: Unit debugging step 12 is “reserved function”.   
The master module display is as below. Then the unit automatically enters into the next step.   
Meaning 
Progress 
Code 
Display 
Display 
Code
Display 
——
 
Step 16: After the unit debugging method is confirmed, the system automatically selects cooling 
or heating mode according to the ambient temperature. 
Once cooling/heating mode is selected, the relevant display is as below.