GMV DC Inverter VRF 
65 
Debugging Parameter Reference Value for DC Inverter VRF Unit
 
12
 
 
 
 
 
 
System 
parameter
 
 
 
 
 
Outdoor 
unit's 
parameter
 
 
Drive bus voltage of 
inverter compressor 
V 
●
  The normal bus voltage is 1.414 times of the 
power supply voltage. For example, if the 
three-phase power supply voltage is 390V, then 
the rectified bus voltage is: 390V 
×
  1.414 = 
551V. The normal deviation between the 
measured value and the calculated value within 
—— 
13
Fan operation 
frequency   
Hz 
●
  Adjust the operation in the range of 0~90Hz 
according to the system pressure adjustment. 
——
 
14
Indoor 
unit's 
parameter
Inlet tube temperature 
of indoor heat 
℃
 
●
  According to the ambient temperature, the 
inlet temperature is 1
℃
~7
℃
  lower than the 
outlet temperature for the same indoor unit 
under cooling mode. 
 
●
The inlet temperature is 1
℃
~7
℃
 
the outlet temperature for the same indoor unit 
—— 
15
of indoor heat 
exchanger   
℃
  —— 
16
Opening of indoor 
electronic expansion 
valve   
PLS
●
  2000PLS electronic expansion valve: the 
opening is adjusted automatically in the range of 
200~2000PLS; 
●
  480PLS electronic expansion valve: the 
opening is adjusted automatically in the range of 
70~480PLS. 
—— 
17
Drainage 
system 
——  — 
●
  The indoor unit drains smoothly and 
thoroughly, and the condensate water pipe has 
no slope water storage; the outdoor unit can 
drain water from the drain pipe without dripping 
directly from the unit foundation. 
—— 
18
Other  ——  —
 
●
There is no abnormal noise for the operation 
of the compressor, indoor fan and outdoor fan. 
The unit is running normally. 
—— 
5 Operation Instruction   
For instructions on how to use the air conditioner, please refer to the  user manual of wired 
controller or remote controller.   
6 Maintenance   
Regular inspection and maintenance can extend the service life of the air conditioning unit. 
6.1 Heat Exchanger of Outdoor Unit 
The heat exchanger of outdoor unit should be cleaned regularly. A vacuum cleaner can be used 
with a nylon brush to clean dust and debris from the surface of the heat exchanger. If there is 
compressed air source, the compressed air can be used to blow dust from the surface of the heat 
exchanger. Do not wash it with tap water. 
6.2 Drain Pipe 
The drain pipe should be checked regularly to allow the condensate to drain smoothly.