GREE GMV5 INDOOR UNIT SERVICE MANUAL
61
Press and hold the FUNCTION button for five seconds
in power-on or power-off status to enter
the parameter query interface C00.
Continuously press the MODE button for three times, and
then press and hold the FUNCTION button for five seconds
to enter the engineering parameter
setting interface. The temperature area displays P00.
Press
to switch to P42.
Single IDU: Press the MODE button. The project number blinks in the timer area. Press or
to adjust the project number, and then Press the ENTER button to confirm and return to
the upper-level menu.
One-to-many: Press the MODE button to enter the IDU selection menu. Press or to
switch IDUs. Press the MODE button to set the project number of the current IDU in the same
method as above.
5.1.3 User Parameter Query
User parameters can be queried in power-on or power-off status.
(1) Press and hold the FUNCTION button for five seconds to enter the user parameter query
interface. The temperature area displays C00 and View is on.
(2) Select a parameter code by pressing or .
(3) Press the ENTER/CANCEL button to return to the upper-level menu till quitting parameter
query.
The user parameter query list is as follows:
Table 2.1 User Parameter Query List
Parameter
Code
Parameter Name
Parameter
Range
View Method
C00
Parameter setting
ingress
-
Display mode:
Timer area: displays the project number of the current IDU.
Note: If the current HBS network consists of multiple IDUs,
only the IDU that has the minimum project number is
displayed.
C01
Project number
query of IDU and
faulty IDU location
1-255: project
number of
online IDU
Operation method:
In C01 status, press the MODE button to enter project
number query of IDU. Press “▲” or “▼” to switch the IDU SN.
Display mode:
Temperature area: displays the fault of the current IDU (in the
case of multiple faults, they are circularly displayed every three
seconds).
Timer area: displays (project number conflict C5 fault)/project
number of the current IDU (project numberes are arranged from
small to large).
Special operations:
After users press the MODE button to enter project number
query, the buzzer of the IDU operated by the wired controller
will ring till users quit C01 query or switch to the next IDU.
C03
Indoor unit
quantity query in
the system
network
1-80
Timer area: displays the number of IDUs in the system
network.

Table of Contents

Other manuals for Gree GMV-ND180PHS/B-T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-ND180PHS/B-T and is the answer not in the manual?

Gree GMV-ND180PHS/B-T Specifications

General IconGeneral
BrandGree
ModelGMV-ND180PHS/B-T
CategoryAir Conditioner
LanguageEnglish

Related product manuals