MULTI VRF-Ⅱ INDOOR UNIT SERVICE MANUAL EUROPEAN/LATIN AMETICA (R410A)
61
Press the “ENTER/CANCEL”
button to confirm settings and
return to the upper-level menu.
Display mode:
Temperature area: displays the
target outlet temperature of fresh-
air IDU.
The setting for
AHU-KIT indoor
unit reach the
temperature in
heating code,
Defrosting in
heating code, oil
return in heating
code
00: indoor fan stop
01: indoor fan keep
operate
When set "00", the same control
with normal GMV indoor unit, the
indoor fan will stop; when set
"01",the indoor fan keep operate.
Note: This setting only aim to AHU-
KIT indoor unit.
Linked settings
for fresh-air IDU
00: no linked control
(default)
There is not linked control by
default upon factory departure.
After the linked control function is
set, the fresh-air IDU can be
independently controlled.
System
conservation
operation
settings
00: comfortability
preferred
01: conservation
preferred
Defrosting period
settings
50: 50 minutes
60: 60 minutes
After settings, it automatically
restores to "00".
Highest capacity
output limitation
settings for ODU
Enter query in “n4” status. The
temperature area displays the
function code and the timer area
displays the corresponding function
setting value.
01-09: intelligent
nighttime silent mode
10-12: forcible silent
mode
Enter query in “A7" status. The
temperature area displays the
function code and the timer area
displays the corresponding function
setting value.
Note:
In parameter setting status, "FAN", “TIMER”, "SLEEP", and "SWING" are invalid. By pressing the
“ON/OFF” button, users can return to the main interface but not power on/off the unit.
In parameter setting status, signals of the remote controller are invalid.
5.1.7 Failure Display
When a fault occurs during the system operation, the temperature area of wired controller displays the
fault code. When multiple faults occur, fault codes are circularly displayed.
When a fault occurs, power off the unit and ask for professional maintenance personnel for help.
The following figure shows the power-on high-pressure protection fault interface.