MULTI VRF- INDOOR UNIT SERVICE MANUAL EUROPEAN/LATIN AMETICA (R410A)
87
3.5.4 Selection of air switch and power cord
Model
Power Cord Size
Air Switch
apacity
(A)
Minimum Sectional
Area of
Ground Wire
(mm
2
/AWG)
Minimum Sectional
Area of Power
Cord
(mm
2
/AWG)
GMV-ND22T/B-T
220~240V/50Hz
208~230V/60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND28T/B-T
220~240V/50Hz
208~230V/60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND36T/B-T
220~240V/50Hz
208~230V/60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND45T/B-T
220~240V/50Hz
208~230V/60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND50T/B-T
220~240V/50Hz
208~230V/60Hz
6
1.0/AWG18
1.0/AWG18
GMV-ND56T/B-T
220~240V/50Hz
208~230V/60Hz
6
1.0/AWG18
1.0/AWG18
3.6 Installation of Compact 2-way Cassette Type unit
3.6.1 Outline and installation dimension
Unit: mm/inch
Model
Indoor
unit(A)
Suspension bolt
pitch(B)
Ceiling
opening(C)
Decoration
panel(D)
Outer diameter of
connection pipe(mm)
Liquid pipe
Gas pipe
GMV-ND28TS/A-T
1200
1252
1403
1443
6.35
9.52
GMV-ND36TS/A-T
GMV-ND45TS/A-T
GMV-ND50TS/A-T
1200
1252
1403
1443
6.35
12.7
GMV-ND56TS/A-T
GMV-ND63TS/A-T
GMV-ND71TS/A-T
1200
1252
1403
1443
9.52
15.9