MULTI VRF- INDOOR UNIT SERVICE MANUAL EUROPEAN/LATIN AMETICA (R410A)
109
Secure a downward gradient of 1/100 or more for the drain pipe. To accomplish this, mount supporting
brackets at an interval of 1 - 1.5 m.(take the cassette type unit for example)
4.4 Testing of Drain Piping
After piping work is finished, check if drainage flows smoothly.
Shown in the figure, Add approximately 1liter of water slowly into the drain pan and check drainage flow
during COOL running.