Instruction of the GMV D.C. inverter
19
manifold and then passes the throttling component for decrease of pressure and temperature. The 
liquid then enters the heat exchanger of the indoor unit and carries out heat exchange with the 
room air to be regulated. The liquid then changes into low-temperature and low-pressure gas. Such 
cycle repeats again and again to achieve the purpose of cooling. When the system turns to heating 
operation, the 4-way reversing valve with solenoid coil shall be started to cause the heating cycle 
follows an adverse course compared with the course of the cooling cycle. The refrigerant radiates 
heat in the heat exchanger of the indoor unit (the electric heating component also starts operation 
and radiates heat) and absorbs heat from the heat exchanger of the outdoor unit to carry out heat 
pump heating cycle for the purpose of heating.
8 Types of Indoor Units to Be Integrated
Diagram of System Integration
Ducted Indoor Unit
(Rectangular Air Outlet) 
Single Side Air
Supply Indoor Unit 
Cassette Indoor Unit 
Wall-Mounted
Indoor Unit 
Floor Standing 
Indoor Unit
Mini D.C.Inverter multi-connected air-conditioning unit consists of one outdoor unit and up to 
16 indoor units. The indoor unit can be of cassette type,single side air supply type,wall-mounted 
type, ducted type, and oor standing type, etc. The wall-mounted type and the oor standing type 
indoor units are controlled by remote controller; the ducted indoor unit is controlled by remote 
controller and wire controller. For the cassette indoor unit and single side air supply cassette indoor 
unit, remote controller or wire controller can be freely chosen. When any indoor unit receives an 
operation order, the outdoor unit shall start operation; when all indoor units stop operation, the 
outdoor unit shall stop.