Gree GMV6 DC Inverter VRF Units Service Manual
198
Possible reasons:
Poor contact between IFD feedback side and main board interface terminal
IFD abnormality
Detecting circuit is abnormal
Troubleshooting:
Yes
”yA” IFD error
If it is loosened or there are
foreign objects, retighten it
after treatment
Detecting circuit might
be abnormal
Yes
Replace the main
control board
No
Replace the IFD directly,
is the error disappeared?
Check the terminal between main
board and IFD to see if it is loose or any
foreign objects inside?
No
2.176
y8
Indoor air box sensor general error
Error display: ODU main board and IDU wired controller will display
Applicable model: IDU with air box
Error judgment condition and method:
Main board, air box communication abnormality and air box test data (temperature, humidity and CO
2
concentration or PM2.5 concentration) has exceeded the set upper and lower limiting value.
Possible reasons:
Poor contact between main control board and air box communication terminal
Air box detection is abnormal
Troubleshooting: