Gree GMV6 DC Inverter VRF Units Service Manual
199
“y8” indoor air box
sensor general error
No
Check if the monitor software
displays air box and the test data
Check if the communication cord
between main control board and air box
loose or any foreign objects inside? If it is
loosened or there are foreign objects,
retighten it after treatment
Is the error disappeared?
Replace the corresponding air box or
monitor software which can’t be
detected, or the air box which the
monitor software displays abnormal
test data
No
Is the error disappeared?
No
Replace the main board
Yes
2.177 Ineffective Cooling and Heating
Applicable models: all indoor units
Fault diagnosis:
1) In cooling mode, when the electronic expansion valve is open to 2000PLS, the temperature of
outlet pipes of the indoor unit coil is over 5°C greater than the temperature of inlet pipes of the
indoor unit coil;
2) In heating mode, when the electronic expansion valve is open to 2PLS, the temperature of inlet
pipes of the indoor unit coil is over 12°C less than the saturation temperature corresponding to
the high pressure;
Possible causes:
The check valve of the outdoor unit is not opened fully as required.
The unit pipes are clogged.