13
GMV6 DC Inverter VRF Units Technical Sales Guide
Model (integrated unit)
GMV-2245WM/H-X GMV-2295WM/H-X GMV-2349WM/H-X GMV-2405WM/H-X GMV-2460WM/H-X
Model (single unit)
GMV-400WM/H-X+
GMV-615WM/H-X+
GMV-615WM/H-X+
GMV-615WM/H-X
GMV-450WM/H-X+
GMV-615WM/H-X+
GMV-615WM/H-X+
GMV-615WM/H-X
GMV-504WM/H-X+
GMV-615WM/H-X+
GMV-615WM/H-X+
GMV-615WM/H-X
GMV-560WM/H-X+
GMV-615WM/H-X+
GMV-615WM/H-X+
GMV-615WM/H-X
GMV-615WM/H-X+
GMV-615WM/H-X+
GMV-615WM/H-X+
GMV-615WM/H-X
Rated power input kW
21+27.41+
27.41+27.41
22+27.41+
27.41+27.41
26.3+27.41+
27.41+27.41
26.85+27.41+
27.41+27.41
27.41+27.41+
27.41+27.41
Rated current A
37.5+49+
49+49
39.3+49+
49+49
47+49+
49+49
48+49+
49+49
49+49+
49+49
Max. fuse current A
40+50+
50+50
40+50+
50+50
50+50+
50+50
50+50+
50+50
50+50+
50+50
NOTES:
a. Rated cooling capacity test conditions: indoor 27
DB/19
WB, outdoor 35
DB; connection pipe
length: 5 m, without height drop between units.
b. Rated heating capacity test conditions(Tdesingnh): indoor 20
DB, outdoor -10
DB/-11
WB;
connection pipe length: 5 m, without height drop between units. Max heating capacity test conditions:
indoor 20
DB, outdoor 7
DB/6
WB; connection pipe length: 5 m, without height drop between
units.
c. The total capacity of connected indoor units must be in the range of 50%~135% of the outdoor unit
capacity. The relevant parameters can be corrected by referring to the unit capacity correction table.
d. The above parameters are tested based on the standard connection pipe length. In the actual project,
the parameters should be corrected referring to the capacity correction for the long connection pipe of
units.
e. Specifications may be changed due to product improvement. Please refer to nameplates of the units.