GREE U-Match 5 SERIES UNIT SERVICE MANUAL
101
Removal of electronic expansion valve
Note: Before removing the electronic expansion valve, make sure there is no refrigerant in the pipeline and power is cut off.
4. Take out the electronic
expansion valve.
●Take out the electronic expansion
valve.
5. Install the new electronic
expansion valve.
●Weld the connection pipe of
electronic expansion valve.
●When welding the electronic
expansion valve, the valve should
be wrapped with wet cloth.
●Nitrogen welding: the pressure of
nitrogen is 0.5±0.1kgf/ c ㎡
(relative pressure). Note: When
welding the pipes, do not let the
flame burn the other components.
●Install the coil of electronic
expansion valve.
6. Secure the electric box and
arrange the wires as required.
●Put the electric box back in place
and tighten up the screws.
●Arrange the wires as original.