EasyManuals Logo

Gree GUD35PS/A-T Service Manual

Gree GUD35PS/A-T
195 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
GREE U-Match 5 SERIES UNIT SERVICE MANUAL
41
3.4 Troubleshooting
3.4.1 ―E1‖ Compressor High Pressure Protection
Error display: ODU mainboard, IDU wired control and IDU receiver light board will display E1
Error judgment condition and method:
It is judged through the action of high pressure switch. If the high pressure switch is cut off, it is judged that high pressure is too
high and the system stops operation for protection.
Possible reason
■Cut-off valve of ODU is not fully opened;
■High pressure switch is abnormal;
■Outdoor or indoor fan is not working properly;
■IDU filter or air duct is blocked (heating mode);
■Ambient temperature is too high;
■Refrigerant charging amount is too much;
■System pipeline is blocked

Table of Contents

Other manuals for Gree GUD35PS/A-T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GUD35PS/A-T and is the answer not in the manual?

Gree GUD35PS/A-T Specifications

General IconGeneral
BrandGree
ModelGUD35PS/A-T
CategoryAir Conditioner
LanguageEnglish

Related product manuals