Troubleshooting: 
 
3.4.2 ―E2‖ Indoor Anti-freezing Protection 
Error display: IDU wired control and IDU receiver light board will display E2 
Error judgment condition and method: 
Check IDU pipe temperature. When pipe temperature is too low, freeze protection will be activated to prevent freezing damage 
of evaporator. 
Possible reason: 
■IDU filter and evaporator are dirty 
■IDU motor is blocked 
■Refrigerant amount is insufficient