GREE                                                                                                    U-Match 5 SERIES UNIT SERVICE MANUAL
 
46 
 
■Connected wired controller quantity or address setting is improper 
■Controller is abnormal 
Troubleshooting: 
 
 
3.4.6 ―E8‖ Indoor Fan Error 
Error display: IDU wired control and IDU receiver light board will display E8 
Error judgment condition and method: 
Check if the rotation speed of IDU is too slow, or it stops rotation, or protection signal of outdoor fan is transferred. If yes, it is 
judged that indoor fan protection occurs 
Possible reason: 
■Motor stops operation or it is blocked 
■IDU mainboard is abnormal;