P0 Driver reset protection
3.3V drive board
voltage is normal or
not?
Replace the drive board
Re-arrange the wires. Heavy
current wires s hould avoid
the drive board chip.
NO
YES
 
3.4.27 ―P5‖ Over-Current Protection 
Error display: ODU mainboard, IDU wired control and IDU receiver light board will display P5 
Error judgment condition and method: 
If compressor‘s instant current value is higher than the set current protection value, then it can be judged that 
compressor over-current occurs and system will shut down for protection. 
Possible reason: 
■System load is too much and compressor current is too large.   
■Compressor 3-phase wire connection is lack of phase or phase-reversed. 
■Compressor phase wire is loose or has bad contact. 
■Drive  board  current  sampling  circuit  element  is  damaged  or  drive  chip  current  sampling  AD  terminal  is 
abnormal. 
■Compressor is damaged.