48
Installation and Maintenance
Service Manual
Safety Precautions for Installing and Relocating the Unit:
To ensure safety, please be mindful of the following precautions. 
1. When installing or relocating the unit, be sure to keep the 
refrigerant circuit free from air or substances other than the 
specied refrigerant.
Any presence of air or other foreign substance in the refrigerant 
circuit will cause system pressure rise or compressor rupture, 
resulting in injury.
2.  When  installing  or  moving  this  unit,  do  not  charge  the 
refrigerant which is not comply with that on the nameplate or 
unqualied refrigerant.
Otherwise, it may cause abnormal operation, wrong action, 
mechanical malfunction or even series safety accident.
3. When refrigerant needs to be recovered during relocating 
or  repairing  the  unit,  be sure  that  the  unit  is running  in 
cooling  mode.Then,  fully  close  the  valve  at high  pressure 
side (liquid valve).About 30-40 seconds later, fully close the 
valve  at  low  pressure side (gas  valve),  immediately  stop 
the unit and disconnect power. Please note that the time for 
refrigerant recovery should  not exceed 1 minute. 
If refrigerant recovery takes too much time, air may be sucked in 
and cause pressure rise or compressor rupture, resulting in injury. 
4. During  refrigerant  recovery, make  sure  that  liquid  valve 
and  gas  valve are  fully  closed  and  power  is  disconnected 
before detaching the connection pipe. 
If compressor starts running when stop valve is open and 
connection pipe is not yet connected, air will be sucked in and 
cause pressure rise or compressor rupture, resulting in injury.
5. When  installing  the  unit,  make  sure  that  connection pipe 
is securely connected before the compressor starts running.
If compressor starts running when stop valve is open and 
connection pipe is not yet connected, air will be sucked in and 
cause pressure rise or compressor rupture, resulting in injury.
6. Prohibit installing the unit at the place where there may be 
leaked corrosive gas or ammable gas.
If there leaked gas around the unit, it may cause explosion and 
other accidents.
7.  Do  not  use  extension  cords  for  electrical  connections.  If 
the  electric  wire  is  not  long  enough,  please  contact  a  local 
service center authorized  and ask for a proper electric wire.
Poor connections may lead to electric shock or re.
8. Use the specied types of wires for electrical connections 
between  the  indoor and  outdoor  units.  Firmly  clamp the 
wires so that their terminals receive no external stresses.
Electric  wires  with  insufcient  capacity,  wrong  wire  connections 
and insecure wire terminals may cause electric shock or re.
WARNINGS