H3 or E4 is displayed
30min after power off the unit
If the overload protector SAT 
      is well connected?
                    Under ambient temperature, 
test the resistance of overload protector with ohmmeter; 
                resistance value should be<1000ohm
If the wiring terminal FA of electronic 
expansion valve is well connected?
 Replace EKV coil of electronic expansion valve
Check the situation of refrigerant; if there is leakage, 
please charge refrigerant according to the service 
manual
Compressor overload protection terminal is not 
connected well with the mainboard; reconnect 
them correctly
Heat exchange of unit is not good (heat exchanger 
is dirty and unit radiating environment is bad);
improve the radiating environment and clean the 
heat exchanger
Too much load of the system causes high temperature
 of compressor after working for a long time; 
decrease the load for operation
Is the malfunction 
    eliminated?
Is the malfunction 
    eliminated?
Is the malfunction 
    eliminated?
Is the malfunction 
    eliminated?
Is the malfunction 
    eliminated?
Replace outdoor 
mainboard AP1
End
Replace overload 
protector SAT
Connect wire 
according to wiring 
diagram
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No