Installation and Maintenance
Service Manual
(1) 
Malfunction of Desynchronizing of Compressor (H7)
Main check point:
Whether the system pressure is too high? 
Whether the electronic expansion valve can work normally?
Whether the radiation for the unit is in good condition?
Malfunction diagnosis process:
Outdoot Unit
Desynchronizing malfunction 
occurs after de-energizing 
and turning on the unit  
Whether stop time for 
compressor is more than 3min?
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Whether valve of outdoor unit is 
opened?
Whether wire connection for 
compressor is correct?
Open the valve
Is malfunction eliminated?
Connect wire correctly
Is malfunction eliminated?
Replace electronic 
expansion valve
Is malfunction eliminated?
End
Replace compressor
Is malfunction eliminated?
Replace main board of 
outdoor unit
Whether electronic expansion 
valve is damaged?