61
Installation and Maintenance
Service Manual
(9) 
Malfunction of Failure Start-up of Compressor (LC)
Main check point: 
Whether the compressor wires are connected correctly?
Whether the stop time for compressor is enough?
Whether compressor is damaged?
Whether the refrigerant-charging volume is superuous?
Malfunction diagnosis process:
Energize and turn 
on the unit
Whether the stop time for 
compressor is more than 3min?
Whether compressor wires are 
connected correctly?
The stop time for unit is not 
enough; high pressure and 
low pressure of system are 
unbalanced; please wait for 
3min and then restart up the unit 
Whether the refrigerant volume 
is superuous?
Please charge the refrigerant 
according to Service Manual
Is malfunction eliminated?
Replace main board of 
outdoor unit
Is malfunction eliminated?
Replace compressor
End
Connect compressor wires 
according to wiring diagram
Is malfunction eliminated?
Yes
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes