When Tambient≥Tset+2°C, the unit will start in cooling mode; In this case, the compressor starts and
indoor fan runs at set speed. After 20s, 4 way valve for cooling start running.
When Tambient≤Tset-2°C, the unit will stop during cooling operation; In this case, the compressor stops
and indoor fan runs at set speed. The 4-way valve for cooling remains original state.
When Tset-2°C<Tambient<Tset+2°C, the unit will operate in the state that the compressor starts 6min and
then stops 4min in cycle. In this case, indoor fan runs at low speed and the 4-way valve for cooling is always
running.