EasyManua.ls Logo

Gree HNTF24/A-D

Gree HNTF24/A-D
45 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4
Condensing Unit
Service Manual
PRODUCT
4 PRODUCT DATA
4.1 Product Data at Rated Condition
HNTF24/A-D HNTF36/A-D HNTF48/A-D HNTF60/A-D
Product Code EM116N0760 EM116N0780 EM116N0800 EM116N0820
Blower
Diameter(inch) 5 5 6 6
Width(inch) 4 4 7 7
Coil Drain Connection
FPT(inch)
7/8 7/8 7/8 7/8
Liquid(inch) 3/8 3/8 3/8 1/2
Suction(inch) 5/8 3/4 7/8 7/8
Electrical Data
Voltage(V) 220-230 220-230 220-230 220-230
Min Circuit
Ampacity (A)
13 13 13 13
Max .Overcurrent
Device(A)
15 15 15 15
Min volts (V) 198 198 198 198
Max volts (V) 254 254 254 254
Fan motor
FLA 0.65 0.65 1.6 1.6
Power output (HP) 1/15 1/15 1/5 1/5
Dimension
Outline Dimension
(W/H/D)(mm)
1220*225*700 1220*225*700 1420*245*700 1420*245*700
Package Dimension
(W/H/D)(mm)
1343*315*823 1343*315*823 1548*345*828 1548*345*828
Net Weight(kg) 41 41 50.5 50.5
Gross Weight(kg) 50 50 58.5 58.5
Note:
a. Nominal capacities are based on the follow conditions.
Indoor Outdoor
Cooling
DB:27
o
C(80.6
o
F)
WB:19
o
C(66.2
o
F)
DB:35
o
C(95
o
F)
WB:24
o
C(75.2
o
F)
Piping Length 7.6m
b. The air volume is measured at the relevant standard external static pressure.
c. Noise is tested in the Semianechoic Room, so it should be slightly higher in the actual operationdue
to environmental change.
4.2 Operation Range
Mode Range of Outdoor Temperature
o
C (
o
F)
Cooling 67-115

Related product manuals