5
Condensing Unit
Service Manual
PRODUCT
4.3 Electrical Data
Indoor unit
Power Supply Fan Motor FLA
Fuse/Breaker
Capacity
Min. Power
Supply Cord
V/Ph/Hz A A mm
2
HNTF24/A-D 220-230,1,60 0.65 15 1.3
HNTF36/A-D 220-230,1,60 0.65 15 1.3
HNTF48/A-D 220-230,1,60 1.6 15 1.3
HNTF60/A-D 220-230,1,60 1.6 15 1.3
Notes:
RLA:Rated load amperes
LRA:Locked rotor amperes
FLA:Full load current
a. Install the disconnect device with a contact gap of at least 3mm in all poles nearby the units (Both
indoor unit and outdoor unit).The appliance must be positioned so that the plug is accessible.
b. The specications of the breaker and power cable listed in the table above are determined based on
the maximum power (maximum amps) of the unit.
c. The specications of the power cable listed in the table above are applied to the conduit-guarded
multi-wire copper cable (like, YJV copper cable, consisting of PE insulated wires and a PVC cable jacket) used
at 40°С and resistible to 90°С(see IEC 60364-5-52). If the working condition changes, they should be modied
according to the related national standard.
d. The specications of the breaker listed in the table above are applied to the breaker with the working
temperature at 40°С. If the working condition changes, they should be modied according to the related national
standard.