1.4 BACnet standard objects
ANSI/ASHRAE 135-2008 defines 30 BACnet standard objects as shown in the standard
document�
Clause Description Page Clause Description Page
12�1 Accumulator Object Type 132 12�16 Life Safety Zone Object Type 203
12�2 Analog Input Object Type 140 12�17 Loop Object Type 209
12�3 Analog Output Object Type 145 12�18 Multi-state Input Object Type 216
12�4 Analog Value Object Type 150 12�19 Multi-state Output Object Type 220
12�5 Averaging Object Type 155 12�20 Multi-state Value Object Type 224
12�6 Binary Input Object Type 158 12�21 Notication Class Object Type 229
12�7 Binary Output Object Type 163 12�22 Program Object Type 232
12�8 Binary Value Object Type 169 12�23 Pulse Converter Object Type 237
12�9 Calendar Object Type 174 12�24 Schedule Object Type 244
12�10 Command Object Type 176 12�25 Trend Log Object Type 249
12�11 Device Object Type 180 12�26 Access Door Object Type 257
12�12 Event Enrollment Object Type 188 12�27 Event Log Object Type 264
12�13 File Object Type 193 12�28 Load Control Object Type 270
12�14 Group Object Type 195 12�29 Structured View Object Type 279
12�15 Life Safety Point Object Type 197 12�30 Trend Log Multiple Object Type 281
1.5 BACnet services
BACnet services are divided into ve segments:
1) Alarm and event Services
2) File Access Services
3) Object access Services
4) Remote device management Services
5) Virtual terminal Services
For each device prole certain services are mandatory.
1.6 Description of a service: BIBB
BACnet Interoperability Building Blocks (BIBBs) are collections of one or more BACnet
services. These are prescribed in terms of an "A" and a "B" device. Both of these devices are
nodes on a BACnet internetwork. In most cases, the "A" device will act as the user of data (client),
and the "B" device will be the provider of this data (server). In addition, certain BIBBs may also be
predicated on the support of certain, otherwise optional, BACnet objects or properties and may
place constraints on the allowable values of specic properties or service parameters.