BACnet Gateway Kit for Central Air Conditioners
21
Device Management-DeviceCommunicationControl-B DM-DCC-B
Device Management-TimeSynchronization-B DM-TS-B
Device Management-UTCTimeSynchronization-B DM-UTC-B
Device Management-ReinitializeDevice-B DM-RD-B
Device Management-Backup and Restore-B DM-BR-B
Device Management-Restart-B DM-R-B
Device Management-List Manipulation-B DM-LM-B
Device Management-Object Creation and Deletion-B DM-OCD-B
3) Network Management BIBBs
Network Management-Connection Establishment-B NM-CE-B
Network Management-Router Conguration-B NM-RC-B
2.4 Segmentation Capability:
Able to transmit segmented messages Window Size 16
Able to receive segmented messages Window Size 16
2.5 Standard Object Types Supported:
1) Standard Object Types Supported: Analog-Input-Object
Dynamically
Creatable
Dynamically
Deleteable
Optional Properties
Supported
Writable Properties
Proprietary
Properties
Description
Device Type
Reliability
Update_Interval
Min_Pres_Value
Max_Pres_Value
Resolution
COV_Increment
Time_Delay
Notication_Class
High_Limit
Low_Limit
Deadband
Limit_Enable
Event_Enable
Acked_Transitions
Notify_Type
Event_Time_Stamps
Present_Value
COV_Increment
Time_Delay
High_Limit
Low_Limit
Deadband
Limit_Enable
Event_Enable