101
H7
Error Code Diagnostics
H7 Error Code, continued on next page
Start Troubleshooting after unit 
is powered off for 3 minutes
Are the compressor terminal 
connected properly?
Yes
Correct wiring 
problem
Remove Malfunction?
No
Replace Compressor
Replace Control Board AP1
No
End Troubleshooting
Desynchronizing of compressor
Status:
During cooling mode, compressor will stop, 
indoor fan will run. Heating mode all units 
stop.
1. Check the resistance of the compressor
terminals and connections to the compressor
2. Check for overcharge of refrigerant
3. Check for correct voltage
4. Check for dirty coils and lters
Troubleshooting Procedure for Synchronizing Fault after Unit is Started
Yes
Compressor Connector