5
Note: The manufacturer reserves the right to modify the design and/or change the specications without notice. Please
refer to specic installation manual for current information.
Physical & Electrical Data, cont.
Model MULTI18HP230V1A MULTI24HP230V1A
System Type Heat Pump
Power Supply 208-230V / 60Hz 208-230V / 60Hz
Rated Current Cooling Amps 7.6 13.5
Rated Current Heating Amps 7.5 12.4
System Performance
Cooling Cap (Min/Max) Btu/h 18,000(7,000-21,000) 26,000(7,500-33,000)
Heating Cap (Min/Max) Btu/h
19,000(8,530-22,600) 29,000(7,500-35,000)
Operating Range - Cooing deg F
23 - 118 23 - 118
Operating Range - Heating deg F 5 - 80 5 - 80
System Specications
Compressor Type DC Inverter-driven Twin Rotary
Sound Level db 56 56
Unit Dimensions (WxHxD)
inches 35.4 x 23.5 x 14.9 37.2 x 27.6 x 15.6
Net/Gross Weight lb 95 / 106 135 / 146
ID & OD Coil Type
Acrylic Resin / Anti-Corrosion Coated
Max # Connectible Indoor
Units
2 3
Refrigerant/Charge oz R410a / 47.6 R410a / 77.6
Port Size (Liquid - Suction) inches
1/4” - 3/8” 1/4” - 3/8”
1/4” - 3/8” 1/4” - 3/8”
1/4” - 3/8”
Pre-Charged Lineset Ft. Feet
33 98
Additional Refrigerant
charge/additional feet
oz 0.2 0.2
Max. Total Piping Length Feet 66 230
Max. Equivalent Length
(Outdoor to last indoor unit)
Feet 33 66
Max. Elevation Feet 33 66
MCA Amps
13
20
MOP Amps 20 30
Note: The manufacturer reserves the right to modify the design and/or change the specications without notice. Please
refer to specic installation manual for current information.