A. Hot gas is discharged from the compressor. e temperature of the gas in monitored by the Discharge
Temperature sensor and sent to the outdoor control panel.
B. e hot gas is directed through the 4-way valve, then enters the outdoor coil. e hot gas will be slightly
subcooled, however there are no pressure ports to take measurements.
C. e subcooled liquid will enter the lter to remove contaminates.
D. e subcooled liquid will enter the Electronic Expansion Valve (EEV) to the appropriate indoor unit and will
regulate to about a 10 degree F superheat level. e EEV will adjust its ow based upon the temperature
sensor readings. e adjustment process and compressor speed are controlled by the outdoor circuit board.
E. e refrigerant leaving the EEV will be in a low pressure/temperature saturated state. is cold saturated
refrigerant will move through the coil absorbing heat. is liquid will ash to a vapor and will be superheated
to about 10 degrees F. Since this tubing is cold, it must be insulated.
F. e superheated vapor will be returned to the outdoor unit’s 4-way valve.
G. e refrigerant will ow to the accumulator (not all models will have an accumulator) where liquid and vapor
are separated.
H. e refrigerant will ow to the compressor and complete another refrigeration cycle.
e control board will monitor the temperature and pressures and adjust the frequency of the compressor and
ow rate of the EEV as needed. ere are no pressure charts to evaluate temperature or pressures.
Product Introduction
Cooling Mode