7
Note: The manufacturer reserves the right to modify the design and/or change the specications without notice. Please
refer to specic installation manual for current information.
Physical & Electrical Data, cont.
Model MULTI42HP230V1A
System Type Heat Pump
Power Supply 208-230V / 60Hz
Rated Current Cooling Amps 19.5
Rated Current Heating Amps 20.5
System Performance
Cooling Cap (Min/Max) Btu/h 41,000 (8,530 - 46,403)
Heating Cap (Min/Max) Btu/h 44,500 (10,663 - 47,768)
Operating Range - Cooing deg F
23 - 118
Operating Range - Heating deg F 5 - 80
System Specications
Compressor Type DC Inverter-driven Twin Rotary
Sound Level db 58
Unit Dimensions (WxHxD)
inches 40 x 43.5 x 17.4
Net/Gross Weight lb 225 / 247
ID & OD Coil Type
Acrylic Resin/Anti-Corrosion Coated
Max # Connectible Indoor
Units
5
Refrigerant/Charge oz R410a / 169.3
Port Size (Liquid - Suction)
.
inches
1/4” - 3/8”
1/4” - 3/8”
1/4” - 1/2”
1/4” - 1/2”
3/8” - 5/8”
Pre-Charged Lineset Ft Feet
168
Additional Refrigerant
charge/additional feet
oz 0.2
Max. Total Piping Length Feet 262
Max. Equivalent Length
(Outdoor to last indoor unit)
Feet 82
Max. Elevation Feet
82
MCA Amps 29
MOP Amps 50