Troubleshooting
Compressor Desynchronizing Malfunction
The unit appears to be
desynchronizing as soon as
energized and starting
Is the stop duration of the
compressor longer than 3 minutes
Is the malfunction corrected
Reconnect wire properly
Is the wiring of the compressor
properly connected
Is the electronic expansion valve
faulty
Replace outdoor main board
Is the malfunction corrected
Replace the compressor
End Troubleshooting
Is the malfunction corrected
Yes
Replace the Electronic expansion
valve
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No