GMV5 Home DC Inverter Multi VRF Units
375
5.2.5 Use of USB Converter
Usage of converter:
Gree commissioning software should be connected with CAN interface when converter is
used. For air conditioners with a single system, connect D1 and D2 interfaces of the wiring board.
For air conditioners with multiple systems, connect G1 and G2 interfaces of the wiring board.