Ultra Heat GMV Multi VRF_Heat Recovery Serial
17
4.3.5.2 Connection sketch map of multi-module system
Fig.21
4.3.5.3 Pipe selection between outdoor unit and the first indoor branch (“L”)
For single module, L pipe between the basic outdoor unit and the first indoor branch:
Basic module
Pipe between outdoor unit and the first indoor branch
Low pressure gas pipe
mm(inch)
Liquid pipe mm(inch)
High pressure gas pipe
mm(inch)
GMV-VQ72W/A-F(U)
Φ28.6(1-1/8)
Φ12.7(1/2)
Φ19.05(3/4)
GMV-VQ96W/A-F(U)
Φ28.6(1-1/8)
Φ12.7(1/2)
Φ19.05(3/4)
For multi-module, L pipe between the terminal outdoor branch and the first indoor branch:
Basic module
Pipe between outdoor unit and the first indoor branch
Low pressure gas pipe
mm(inch)
Liquid pipe mm(inch)
High pressure gas pipe
mm(inch)
GMV-VQ192WM/A-F(U)
Φ31.8(1-1/4)
Φ15.9(5/8)
Φ28.6(1-1/8)
4.3.5.4 ODU pipe size selection for multi-module system
Pipe size between module and outdoor branch M1, M2:
Basic module
Pipe between outdoor unit and the first indoor branch
Low pressure gas pipe
mm(inch)
Liquid pipe mm(inch)
High pressure gas pipe
mm(inch)
GMV-VQ72W/A-F(U)
Φ28.6(1-1/8)
Φ12.7(1/2)
Φ19.05(3/4)
GMV-VQ96W/A-F(U)
Φ28.6(1-1/8)
Φ12.7(1/2)
Φ19.05(3/4)
Selection of branch Y1 connecting to outdoor modules: