Ultra Heat GMV Multi VRF_Heat Recovery Serial
53
confirm the startup again. Operate as below:
If master unit displays as below, system is waiting for confirmation signal.
12_Confirm
debugging startup
If it’s confirmed, press SW4 confirmation button. Then unit will display as below and start next
progress.
12_Confirm
debugging startup
Step 16: After unit is confirmed to start debugging, system select cooling/heating mode according to
ambient temperature automatically.
A If cooling mode is selected, relevant display is as below:
Debugging is enabled in cooling mode
(debugging mode, auto-selected by
system).
ODU Error occurs during debugging in
cooling mode.
System detects error in indoor error.
XXXX is the project code of the faulted
IDU. 3s later, error code is displayed.
For example, IDU no. 100 has d5 error,
then LED3 displays like this: 01 (2s
later) 00 (2s later) d5, and repeat
again.
B If heating mode is selected, relevant display is as below:
Debugging is enabled in heating mode
(debugging mode, auto-selected by
system).
ODU Error occurs during debugging in
heating mode.