Air-to-water Heat Pump Monobloc Versati
8
9
5 Nomenclature
G RS - C Q 16 Pd / Na C - M
1 2 3 4 5 6 7 8 9
NO. Description Options
1 GREE G-GREE Air to water heat pump
2 Heat Pump Water Heater RS
3 Heating Mode S= Static; C=Circulating
4 Function Q=Multi-function; Omit=Single-function
5 Nominal Heating Capacity 6=6.0kW; 8=8.0kW;10=10kW; 12=12kW; 14=14kW; 16=16kW
6 Compressor Style Pd=DC Inverter; Omit=On/Off
7 Refrigerant Na=R410A
8 Design Serial Number B,C,D......
9 Power Supply K=220-240V,~,50Hz; M=380-415V,3N~,50Hz
Model Line-Up
Model Name
Capacity
Power supply
Heating
1
,kW Cooling
2
,kW
GRS-CQ8.0Pd/NaC-K 8.2 8.6
220-240V,~,50Hz
GRS-CQ10Pd/NaC-K 9.5 9.8
GRS-CQ12Pd/NaC-M 13.0 13.6
380-415V,3N~,50Hz
GRS-CQ14Pd/NaC-M 14.2 14.5
Note:
1
Capacities and power inputs are based on the following conditions:
Indoor Water Temperature 30°C/35°C,Outdoor Air Temperature 7°C DB/6°C WB;
2
Capacities and power inputs are based on the following conditions:
Indoor Water Temperature 23°C/18°C,Outdoor Air Temperature 35°C DB/24°C WB.
Operation Range
Mode Heat Source Side Temperature (°C) User Side Temperature (°C)
Heating -20~35 25~60
Cooling 10~48 7~25
Water Heating -20~45 40~80