Gree Versati II+ - Flow Chart Of Troubleshooting; High-pressure Protection E1

Gree Versati II+
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3
Test Operation & Troubleshooting & Maintenance
50 Desynchronizing Desynchronize Pc
51 Compressor stalling Comp. stalling H7
52 Communication error drive-main com. LE
53 Radiator or IPM or PFC module overtemperature Overtemp.-mod. P8
54 Radiator or IPM or PFC module temperature sensor error T-mod. sensor P7
55 Charging circuit error Charge circuit Pu
56 Incorrect AC voltage input AC voltage PP
57 Drive board temperature sensor error Temp-driver PF
58 AC contactor protection or input zero crossing error AC contactor P9
59 Temperature drift protection Temp. drift PE
60
Current sensor connection protection (current sensor not connected to
phase U/V)
Sensor con. PD
61 Communication error to the outdoor unit ODU Com. E6
62 Communication error to the indoor unit IDU Com. E6
63 Communication error to the drive Driver Com. E6
64 Solar kit-superheating Solarsuperheat F6
3 Flow Chart Of Troubleshooting
3�1 Comp High-pressure Protection E1
Comp High-pressure protection E1
Check if the High-pressure switch
is broken
Replace the High-pressure
switch
Check if the High-pressure switch
wiring is loose.
Replace the wiring
Check if the water in
the tank is enough
Check if the installation of
tank temp sensor is correct
Check if the gas valve and
liquid valve are fully open
Check if the electric expansion
valve can work normally
Fill the tank with the water
Install rightly the
tank temp sensor
Fully open the valve
Replace the electronic
expansion valve
yes
no
yes
no
no
no
yes
yes
yes
yes
no