Greyline Instruments DFM-IV - FIELD TROUBLESHOOTING (METER READING TOO HIGH; DOES NOT TRACK FLOW)

Greyline Instruments DFM-IV
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Possible Causes: Corrective Action:
Variable Speed Drive interference
·
Follow Drive manufacturers wiring and
Grounding instructions
·
Relocate Flowmeter electronics, Sensor and
wiring away from VSD
METER READING DOES NOT TRACK FLOW
Sensor and GND wires reversed or not properly
connected
·
Check Sensor connections
Improper AC power input Ground
·
Use direct connection with 12 AWG wire to
nearest Ground pole (<1 ohm resistance).
Page 21
DFM-IV Doppler Flow Meter
Manual Series A.6